KM200/50 Modular Ups Power Supply 200kVA
Parameters for KM200/50
Input Parameters
-
Rated Power: 200kVA
-
Rated Voltage: 380/400/415VAC (L-L), 220/230/240VAC (L-N)
-
Rated Frequency: 50/60Hz
-
Input Power Factor: >0.99
-
Input Current Harmonic Distortion: THDi < 3% (100% linear load)
-
Voltage Range:
-
Frequency Range: 40–70Hz
Battery Parameters
Bypass Parameters
-
Rated Voltage: 380/400/415VAC (L-L), 220/230/240VAC (L-N)
-
Rated Frequency: 50/60Hz
-
Voltage Range: -40% to +25% (adjustable, default: -20% to +15%)
-
Overload Capability:
Inverter Parameters
-
Rated Voltage: 380/400/415VAC (L-L), 220/230/240VAC (L-N)
-
Rated Frequency: 50/60Hz
-
Output Power Factor: 1
-
Voltage Accuracy: ±1.0%
-
Load Response: <5% (20% → 80% → 20% step load)
-
Recovery Time: <20ms (0% → 100% → 0% step load)
-
Output THDu: <1% (linear load), <5% (non-linear load, per IEC 62040-3)
-
Overload Capability:
-
110%: 1 hour
-
125%: 10 minutes
-
150%: 1 minute
- 150%: 200ms
-
Frequency Accuracy: 0.1%
-
Synchronization Window: Adjustable, default ±3Hz
-
Slew Rate: Adjustable, default 0.5Hz/S
-
Crest Factor: 3:1
-
Phase Accuracy: 120°±0.5°
System Parameters
-
Efficiency:
-
Normal Mode: up to 96%
-
Battery Mode: up to 96%
-
Display: LED + 7-inch touch LCD
-
Certifications - Safety: IEC62040-1, IEC60950-1
-
Certifications - EMS: IEC62040-2; IEC61000-4-2 (ESD); IEC61000-4-3 (RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge)
-
IP Rating: IP20
-
Configuration: USB, RS232, RS485, dry contact, cold start, air filter
-
Options: SNMP card, AS400 card, parallel kit, SPD, LBS
-
Environmental Conditions:
-
Operating Temperature: 0°C–40°C
-
Storage Temperature: -25°C–70°C
-
Humidity: 0–95% (non-condensing)
-
Noise: 72dB @ 100% load, 69dB @ 45% load
Dimensions and Weight
-
Cabinet Dimensions (W×D×H) mm: 600×1000×1600
-
Module Dimensions (W×D×H) mm: 442×659×174
-
Weight (kg):
-
Power Module Rated Capacity: 50kW