40kVA 3/3 Three Phase Tower Ups Power Supply With Inner Built Battery
Input Parameters
-
Rated Power: 40kVA
-
Rated Voltage: 380/400/415VAC (L-L), 220/230/240VAC (L-N)
-
Rated Frequency: 50/60Hz
-
Input Power Factor: >0.99
-
Input Current Harmonic Distortion: THDi < 3% (100% linear load)
-
Voltage Range: 304~478VAC (L-L) full load; 304~228VAC (L-L) power derate from 100% to 75%
-
Frequency Range: 40~70Hz
Battery Parameters
-
Battery Voltage: ±240VDC
-
Battery Model: UPS with internal batteries, 12VDC/7-9Ah
-
Battery Quantity: 160PCS
-
External Battery Quantity: Depends on external battery, 40PCS
-
Charging Capacity: 20% Pout
-
Charging Accuracy: ±1%
Bypass Parameters
-
Rated Voltage: 380/400/415VAC (L-L), 220/230/240VAC (L-N)
-
Voltage Range: -40% to +25% (adjustable, default: -20% to +15%)
-
Frequency Range: 50/60Hz (adjustable: ±1Hz, ±3Hz, ±5Hz)
Inverter Parameters
-
Rated Voltage: 380/400/415VAC (L-L), 220/230/240VAC (L-N)
-
Rated Frequency: 50/60Hz
-
Output Power Factor: 1
-
Voltage Accuracy: ±1.0%
-
Load Response: <5% (20% - 80% - 20% step load)
-
Recovery Time: <20ms (0% - 100% - 0% step load)
-
Output THDu: <1% (linear load), <5% (non-linear load according to IEC 62040-3)
-
Overload Capacity: 110%, 1 hour; 125%, 10 minutes; 150%, 1 minute; >150%, 200ms
-
Frequency Accuracy: 0.1%
-
Synchronization Window: Adjustable, default ±3Hz
-
Slew Rate: Adjustable, default 0.5Hz/S
-
Crest Factor: 3:1
-
Phase Accuracy: 120°±0.5°
System Parameters
-
Efficiency: Normal Mode up to 96%; Battery Mode up to 96%
-
Display: LED + 7-inch touch LCD
-
Certifications - Safety: IEC62040-1, IEC60950-1
-
Certifications - EMS: IEC62040-2; IEC61000-4-2 (ESD); IEC61000-4-3 (RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge)
-
IP Rating: IP20
-
Configuration: USB, RS232, RS485, dry contact, air filter
-
Options: SNMP card, AS400 card, parallel kit, LBS, cold start
Environmental Conditions
-
Operating Temperature: 0°C~40°C
-
Storage Temperature: -25°C~70°C
-
Humidity: 0~95% (non-condensing)
Noise
Dimensions and Weight
Characteristics
-
Intelligent Battery Management: Smart battery management system.
-
Wide Input Voltage Tolerance: Adaptable to a broad range of input voltages.
-
3-level Topology: High performance and efficiency.
-
Adapt to Half-wave Load: Suitable for half-wave load conditions.
-
Auto Fault Waveform Recording: Automatic recording of fault waveforms.
-
Online Double Conversion: Full digital control for reliability.
-
Self-aging Function: Energy-saving test function.
-
High Load Adaptability: Output PF=1 for better load adaptability.
-
High Power Density: Compact design for high power output.