Small Computer Room Precision Cooling Units Data Centre Cooling Equipment

Ask Latest Price
Video Channel
Brand Name :kimoems
Model Number :Refer to parameters
Certification :CE
Place of Origin :China
MOQ :1pc
Payment Terms :T/T
Rated Total Cooling Capacity (27°C-50%RH) :8.2/13.2 kW
Total Cooling Capacity (24°C-50%RH) :7.7/12.5 kW
Sensible Cooling Capacity (24°C-50%RH) :7.0/11.3 kW
Compressor Standard Quantity :1
Axial Fan Quantity :2
Axial Fan Airflow :2700/3300 m³/h
Fan Power Consumption :0.25/0.35 kW
Electrical Power Supply :380V-50Hz-3P+N+PE
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Air-cooled Energy-saving Computer Room Precision Cooling For Small Data Centers And Base Stations


Product Introduction

The SDA.HP unit is a type of air-cooled energy-saving computer room air conditioner designed specifically for small data centers and base stations. The unit is equipped with two cooling systems: a gravity-driven heat pipe cooling system and a compressor cooling system. Based on the actual year-round cooling requirements of data centers, the unit automatically selects the appropriate cooling mode. It fully utilizes natural cooling sources during periods of low outdoor temperatures, significantly reducing the unit's annual energy consumption.

Small Computer Room Precision Cooling Units Data Centre Cooling EquipmentSmall Computer Room Precision Cooling Units Data Centre Cooling Equipment

  • The compressor uses mature products from well-known brands, ensuring high efficiency and reliability. It features a scroll design with flexible and low-pressure chamber construction, offering high reliability and low noise.
  • The efficient and reliable microchannel heat exchanger is corrosion-resistant, has a long service life, and can be repeatedly cleaned.
  • The mature tube-fin heat exchanger has high heat exchange efficiency, is corrosion-resistant, high-pressure resistant, and easy to clean.
  • The efficient integrated axial fan provides a large air volume and operates with low noise.


Parameters


Model SDA.HP 81 121
Cooling Capacity (1)


Rated Total Cooling Capacity (27°C-50%RH) kW 8.2 13.2
Total Cooling Capacity (24°C-50%RH) kW 7.7 12.5
Sensible Cooling Capacity (24°C-50%RH) kW 7.0 11.3
Compressor


Standard Quantity n.° 1 1
Compressor Power Consumption kW 2.05 3.20
Compressor Current Consumption A 3.8 6.0
Axial Fan (2)


Quantity n.° 2 2
Airflow m³/h 2700 3300
Static Pressure Pa 0~50 0~50
Fan Power Consumption kW 0.25 0.35
Humidifier (Optional)


Maximum Steam Output kg/h 3 3
Rated Power kW 2.25 2.25
Rated Current A 3.4 3.4
Electric Heater (Optional)


Rated Power kW 3.00 4.00
Number of Stages n.° 1 1
Rated Current A 4.5 6.1
Dimensions and Weight


Length mm 750 750
Width (Depth) mm 650 650
Height mm 1800 1800
Weight kg 183 198
Electrical Parameters


Power Supply
380V-50Hz-3P+N+PE
Full Load Current A 15.20 19.10
Air Switch Specification A 20 20
Indoor Machine Cable Specification mm² 5×4mm² 5×4mm²
Outdoor Machine Cable Specification mm² 3×1.5 3×1.5
Outdoor Unit (3)




RCL12HP RCL14HP
Notes:
  1. Outdoor ambient temperature: 35°C
  2. Axial fan, G4 filter configuration
  3. The indoor and outdoor units must be connected with special piping for the mechanical cooling and heat pipe cooling systems. The outdoor unit must be higher than the top of the indoor unit.
  4. When the outdoor ambient temperature is 5°C, the cooling capacity of the heat pipe alone is 70% of the compressor's rated cooling capacity.
  5. When the outdoor ambient temperature is -5°C, the cooling capacity of the heat pipe alone is 100% of the compressor's rated cooling capacity.
  6. When the outdoor temperature is 15°C or lower, the heat pipe and compressor operate simultaneously, and the cooling capacity can reach 150% of the rated cooling capacity.