3U single power module with power up to 60kW
Single 42U cabinet with capacity up to 600kW
Supports power system N+1
Modular design reduces MTTR (mean time to maintenance)
High scalability
Built-in maintenance bypass switch for easy maintenance and uninterrupted output High-efficiency double-conversion online UPS
Flexible battery configuration and adjustable charging current
High overload capacity power supply walk-in function
| Model | A-I-30U-180 (PM-60) | A-I-42U-300 (PM-60) | A-I-42U-420 (PM-60) | A-I-42U-600 (PM-60) |
| Phase | 3-phase input / 3-phase output | |||
| Power Module Capacity | 180KW | 300KW | 420KW | 600KW |
| Battery Type | External Battery | |||
| One Power Module | 60KVA/60KW | |||
| Number of Power Modules | 3 | 5 | 7 | 10 |
| Connection Method (Rear Connection) | Upward Connection | Upward/Downward Connection | Upward/Downward Connection | Upward/Downward Connection |
| Number of Breakers | 3 | 2 | 2 | 2 |
| Input | ||||
| Rated Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||
| Voltage Range | 110-300 VAC @ 50% load; 176-276 VAC @100% load | |||
| Input Frequency | 50/60 Hz (Automatic Detection) | |||
| Frequency Range | 40Hz ~ 70Hz | |||
| Power Factor | 100% Load>0.99; 50% Load>0.98 | |||
| Harmonic Distortion (THD) | <3% @ 100% Load | |||
| Output | ||||
| Rated Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||
| Voltage Regulation (Stable) | ≤ ±1% (Stable Load) / ≤ ±2% (Unstable Load) | |||
| Frequency | 50/60Hz | |||
| Frequency Range (Synchronization Range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||
| Overload Capacity | 1 hour ≤ 110%; 111% ~ 125% for 10 minutes; 126% ~ 150% for 1 minute; > 150% for 200 milliseconds | |||
| Harmonic Distortion | ≤ 2% THD (Linear Load), ≤ 4% THD (Non-linear Load) | |||
| Efficiency | 96% | |||
| Battery / Charging | ||||
| Rated Voltage | +/- 192V ~ +/- 240V (Optional) | |||
| Maximum Voltage | +/- 240V (12V x 40 cells) | |||
| Minimum Voltage | +/- 192V (12V x 32 cells) | |||
| Floating Voltage | 2.28V / Cell (2.25V to 2.33V Optional) | |||
| Equalizing Voltage | 2.35V / Cell | |||
| Temperature Compensation | Supported | |||
| Maximum Current per Module | 16A (Optional) | |||
| Physical Properties | ||||
| Dimensions (W x H x D) mm | 1100 x 600 x 1475 | 1100 x 600 x 2010 | 1100 x 600 x 2010 | 106 x51000 x 2000 |
| Weight (kg) | 224 | 297 | 308 | 420 |
| Operating Environment | ||||
| Operating Temperature | 0-40°C | |||
| Relative Humidity | 0-95% (Non-condensing) | |||
| Altitude | < 1000m (Standard) | |||
| Protection IP Level | IP 20 | |||
| Software | ||||
| RS-232/485 | Supports Windows,Linux and MAC | |||
| SNMP (Optional) | SNMP card and network management | |||
| Safety Standards | ||||
| Safety | IEC/EN 62040-1 | |||
| Electromagnetic Compatibility | IEC/EN 62040-2 Category C3 | |||
| Model | ||||
| PM-60 | 3 Phase / 3 Output 60KVA/60KW Power Module | |||
| Dimensions (W x H x D) mm | 750x438x130 (3U) | |||
| Weight (kg) | 44 | |||