Add to Cart
APlus Modular UPS (60kW Module) 180kVA 300kVA 420kVA 600kVA
| Model | A+30U-180 (PM-60) | A+42U-300 (PM-60) | A+42U-420 (PM-60) | A+42U-600 (PM-60) |
| Phase | 3-phase Input/3-phase Output | |||
| Cabinet Capacity* | 180kW | 300kW | 420kW | 600kW |
| Battery Type | External Battery | |||
| Power Module Capacity | 60kVA/60kW | |||
| Max Power Modules | 3 | 5 | 7 | 10 |
| Wiring (Rear) | Top Entry | Top/Bottom Entry | Top/Bottom Entry | Top/Bottom Entry |
| Switch Quantity | 3 | 2 | ||
| INPUT | ||||
| Rated Voltage | 3×380/400/415VAC (3PH+N) | |||
| Voltage Range | 110-300VAC @50% load,176-276VAC @100% load | |||
| Nominal Frequency | 50/60Hz (Auto Detection) | |||
| Frequency Range | 40-70Hz | |||
| Power Factor | >0.99 @100% load,>0.98 @50% load | |||
| THDI | <3% @100% load | |||
| OUTPUT | ||||
| Rated Voltage | 3×380/400/415VAC (3PH+N) | |||
| Voltage Regulation (Static) | ≤±1% typical (balanced load),≤±2% typical (unbalanced load) | |||
| Nominal Frequency | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz |
| Frequency Range (Sync) | 46-54Hz or 56-64Hz | |||
| Overload Capacity | ≤110%: 60min;111-125%: 10min;126-150%: 1min;>150%: 200ms | |||
| THD | ≤2% (linear load);<4% (non-linear load) | |||
| Efficiency | 96% | |||
| Battery/Charging | ||||
| Rated Voltage | ±192V-±240V (Selectable) | |||
| Max Voltage | ±240V (12V×40 cells) | |||
| Min Voltage | ±192V (12V×32 cells) | |||
| Float Charge Voltage | 2.28V/cell (2.25-2.33V selectable) | |||
| Equalize Voltage | 2.35V/cell | |||
| Temp. Compensation | Supported | |||
| Max Charging Current (per module) | 16A (Adjustable) | |||
| Physical Specifications | ||||
| Cabinet Dimensions (D×W×H, mm) | 1100×600×1475 | 1100×600×2010 | 1065×1000×2000 | |
| Net Weight (kg) | 224 | 297 | 308 | 420 |
| Operating Environment | ||||
| Operating Temperature | 0-40°C | |||
| Relative Humidity | 0-95% (non-condensing) | |||
| Altitude* | Rated power <1000m | |||
| IP Rating | IP20 | |||
| Control & Management | ||||
| RS-232/USB | Windows series, Linux, Mac | |||
| SNMP (Optional) | SNMP card and browser power management | |||
| Safety Standards | ||||
| Safety | IEC/EN 62040-1 | |||
| EMC | IEC/EN 62040-2 Category C3 | |||
| Note: If the UPS is installed or used at an altitude above 1000m, the output power must be reduced by 1% per 100m. | ||||
| Model | Description | Dimensions (D×W×H, mm) | Weight (kg) | |
| PM-60 | 3-in/3-out 60kVA/60kW Power Module | 750×438×130 (3U) | 44 | |